The normally open DC contactor is an essential component in modern electrical systems, providing a range of features that improve safety, efficiency and reliability. Its ability to effectively control DC circuits makes it an indispensable tool for professionals in a variety of industries. With its high current carrying capacity, fast response speed and durable construction, the normally open DC contactor meets the needs of today’s complex electrical applications. As technology continues to advance, the importance of this type of device will only increase, solidifying its role in the future of electrical engineering.

SAYOON MODEL IMPLICATION

SZJ

400A

-D

-S

-□

-□

/□

1

2

3

4

5

6

7

1

Product type

2

Rated current

3

Coil type: None-Double coils structure; D-Single coil structure

4

Auxiliary switch: None-Without auxiliary switch; S-With auxiliary switch

5

Mounting bracket type: None-M Horizontal (default); E-Level embedded; L(N)-Vertical; E1-Level embedded single direction

6

Other function codes

7

Coil rated voltage: 12V, 24V, 36V, 48V, 60V, 72V etc.

Uses

This product have one normally open contact, for electric vehicles, telecommunication equipment, engineering machinery, car batteries, electric forklift trucks, trains, ships, electronic control systems such as uninterruptible power supply.

Technical Parameters:  (Version 2.53)

 SAYOON Product Type

 SZJ400A-D

 Contact form  1 NO
 Coil Rated voltage (DC V)  6V,12V,24V,36V,48V,60V,72V,84V,120V,150V,220V etc.
 Contact voltage (DC V)  ≤60V
 Rated load current of contact 48V circuit (A)  400A
 Typical voltage drop across contacts per 100A  ≯80mV
 The cooling pull-in voltage at (20±5)℃ (V)  ≯70%
 The cooling drop-out voltage at (20±5)℃ (V)  ≯35%,≮5%
 Working voltage range of 40℃ coil  0.8-1.2Us
 Drop-out time (n/o contacts to open)  35ms
 Pull-in time (n/o contacts to close)  10ms
 Maximum bounce time for contact connection  10ms
 Maximum bounce time for contact disconnection  3ms
 Insulation resistance  20MΩ
 Electric strength to resist  50Hz/60Hz 1000VAC 1minute
 Typical fault currents which can be ruptured  1500A/5ms at 48V DC
 Coil power (W)  9-18
 Temperature rise of coil (K)  ≤60
 Temperature rise on outgoing terminal (K)  ≤65
 Electrical life  20,000 times
 Mechanical life  300,000 times
 Work specification  Continuous
 Contact material  Ag alloy
 Load terminal type  M10 Screw
 Coil terminal type  M4 Screw
 Auxiliary contact rated load (optional)  2A/48VDC, 5A/24VDC
 Testing organization certification  CCC,CE,FCC,RoHS

 

Note:As regarding to the different using environments of customers which requires different focus of the functions,and in order to improve the comprehensive properties of our products,sayoon may adjust the coil parameters,temperature rise and so on. The above parameters are for reference only, For details, please refer to the guidelines for selection and use of the SAYOON DC contactor.

Load Characteristic Curve

  • HEV400 HV DC Contactor detail (3)
  • HEV400 HV DC Contactor detail (2)

Installation Diagram

szj400a-d

Wiring Diagram

szj-10-d_e

Temperature Curve

xqws-szj100a-d

Mechanical Ability And Use Of The Environment

 Contact lead M10 tightening torque (N.m)  ≯20.5 appropriate
 Coil lead M4 tightening torque (N.m)  ≯1.2 appropriate
 Ambient temperature  -25~+70℃
 Relative humidity  +20℃ 98%
 Vibration freq. atthe fixed position  3G, 1~50Hz amplitude 0.5mm
 Concussion  (60~100) time/minute、acceleration≤4g
 Altitude  2000m
 Installation direction  Random
 International Protection  IP40 (According IEC60947)

Order Instruction

 SAYOON Product Type

 SZJ400A-D

 U.N.W.  1019g
 U.G.W.  1040g
 Package QTY.  30PCS
 Mounting bracket type  None – M Horizontal (default), E Level Embedded, L (N) Vertical, E1 Level embedded single direction

 

When ordering, please state the following: name, full model, control coil voltage specification, installation frame type, whether with auxiliary contact, order quantity. For example: DC Contactor SZJ400A-D/24V 100pcs, indicating the load rated current 400A, without auxiliary contact, default mounting bracket, coil control voltage 24V purchase 100pcs. Special voltage specification products, such as user needs can be special order.

Request a Custom Quote

Interested in this product? Fill out the form below and our sales team will get back to you within 24 hours.

Formulario de Contacto
WhatsApp
WhatsApp QR Code
WeChat
WeChat Code
Phone
+86 130 5791 2357
Email
sayoon@sayoon.com