QZJB1000A 1000A Normally Closed DC Contactor: Specifications & Selection
The SAYOON QZJB1000A is a 1000A normally closed dc contactor for DC switching. A normally closed contact carries the circuit in its unenergized state and opens when the coil is actuated. Match this behavior to the control sequence before selecting the coil and mounting version.
- Rated load current
- 1000A at 48V DC
- Contact voltage
- ≤150V DC
- Contact arrangement
- 1 NC
- Coil voltage examples
- 12V / 24V / 48V DC
- Load terminals
- M12 Screw
- Duty type
- Continuous
Applications & selection
Choose a normally closed contactor when the circuit must be connected in the coil-off state. Check what happens during loss of control power, confirm the load type and switching frequency, and verify that the opening duty suits the actual DC voltage and current.
Specify your QZJB1000A configuration
For QZJB1000A, provide the circuit diagram, DC voltage and load current, control supply, duty cycle, required auxiliary contacts and installation dimensions. Ask for the exact terminal drawing and confirmation of ratings for your configuration. See the technical information and drawings below for further details.
FEATURES
SAYOON MODEL IMPLICATION
|
QZJB |
1000A |
-S |
-□ |
-□ |
■ |
/□ |
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
|
|
|
|
1 |
Product type | |||||||
|
2 |
Rated current | |||||||
|
3 |
Auxiliary switch: None-Without auxiliary switch; S-With auxiliary switch | |||||||
|
4 |
Mounting bracket type: M-Horizontal (default) | |||||||
|
5 |
Other function codes | |||||||
|
6 |
Other special functions: V-With capacitive load | |||||||
|
7 |
Coil rated voltage: 12V, 24V, 36V, 48V, 60V, 72V etc. | |||||||
USES
TECHNICAL PARAMETERS: (Version 1.00)
|
SAYOON Product Type |
QZJB1000A |
| Contact form | 1 NC |
| Coil Rated voltage (DC V) | 6V,12V,24V,36V,48V,60V,72V,96V etc. |
| Contact voltage (DC V) | ≤150V |
| Rated load current of contact 48V circuit (A) | 1000A |
| Typical voltage drop across contacts per 100A | ≤80mV |
| The cooling pull-in voltage at (20±5)℃ (V) | ≤70% |
| The cooling drop-out voltage at (20±5)℃ (V) | ≤50%, ≥5% |
| Working voltage range of 40℃ coil | 0.8-1.2Us |
| Drop-out time (n/o contacts to open) | 50ms |
| Pull-in time (n/o contacts to close) | 15ms |
| Maximum bounce time for contact connection | 10ms |
| Maximum bounce time for contact disconnection | 3ms |
| Insulation resistance | 20MΩ |
| Electric strength to resist | 50Hz/60Hz 1000VAC 1minute |
| Typical fault currents which can be ruptured | 2400A/5ms at 48V DC |
| Coil power (W) | Start: 35-65, Keep: 4-10 |
| Temperature rise of coil (K) | ≤40 |
| Temperature rise on outgoing terminal (K) | ≤65 |
| Electrical life | 10,000 times |
| Mechanical life | 200,000 times |
| Work specification | Continuous |
| Contact material | Ag alloy |
| Load terminal type | M12 Screw |
| Coil terminal type | M3 Screw |
Note:As regarding to the different using environments of customers which requires different focus of the functions,and in order to improve the comprehensive properties of our products,sayoon may adjust the coil parameters,temperature rise and so on. The above parameters are for reference only, For details, please refer to the guidelines for selection and use of the SAYOON DC contactor.
LOAD CHARACTERISTIC CURVE
INSTALLATION DIAGRAM

WIRING DIAGRAM

TEMPERATURE CURVE

MECHANICAL ABILITY and USE of the ENVIRONMENT
| Contact lead M12 tightening torque (N.m) | ≯30.0 appropriate |
| Coil lead M3 tightening torque (N.m) | ≯0.8 appropriate |
| Ambient temperature | -25~+70℃ |
| Relative humidity | +20℃ 98% |
| Vibration freq. atthe fixed position | 3G, 1~50Hz amplitude 0.5mm |
| Concussion | (60~100) time/minute、acceleration≤4g |
| Altitude | 2000m |
| Installation direction | Random |
| International protection | IP40 (According IEC60947) |
ORDER INSTRUCTION
|
SAYOON Product Type |
QZJB1000A |
| Mounting bracket type | None – M Horizontal (default) |
Request a Custom Quote
Interested in this product? Fill out the form below and our sales team will get back to you within 24 hours.